IM02601006E www.eaton.com 2-1
IQ 150S/250S 2: Overview and Specifications
2: IQ 150S/250S Submeter Overview and Specifications
2.1: Hardware Overview
Eaton’s IQ 150S/250S submeter is designed to measure
revenue grade electrical energy usage and communicate
that information via various communication media. The unit
supports RS485, RJ45 wired Ethernet or IEEE 802.11 WiFi
Ethernet connections. This allows the submeter to be
placed anywhere within an industrial or commercial facility
and still communicate quickly and easily back to central
software.
The unit is designed with advanced measurement
capabilities, allowing it to achieve high performance
accuracy. The IQ 150S meter is specified as a 0.2% class
energy meter for billing applications (the IQ 250S is so
specified for Class 10 only). To verify the submeter’s perfor-
mance and calibration, power providers use field test stan-
dards to verify that the unit’s energy measurements are correct. The IQ 150S/250S meter is a
traceable revenue meter and contains a utility grade test pulse to verify rated accuracy.
The IQ 250S meter has up to 2 MegaBytes* for datalogging. It offers three
historical logs, a Limits (Alarm) log, and a System Events log.
*NOTE
: Because the memory is flash-based rather than NVRAM (non-volatile
random-access memory), some sectors are reserved for overhead, erase procedures, and spare
sectors for long-term wear reduction.
IQ 150S/250S meter features detailed in this manual are:
• 0.2% Class Revenue Certifiable Energy and Demand Submeter (IQ 250S Class 10 only)
• Meets ANSI C12.20 (0.2%) and IEC 62053-22 (0.2%) Classes (IQ 250S Class 10 only)
• Multifunction Measurement including Voltage, Current, Power, Frequency, Energy, etc.
• Three line 0.56” bright red LED display
• 2 MegaBytes Memory for Datalogging (IQ 250S)
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...