IM02601006E www.eaton.com C-10
IQ 150S C: DNP Map
These points are formatted as 2's complement fractions. They represent a fraction of 4500W Sec-
ondary in normal operation, or 3000W Secondary in Open Delta operation. Inputs above/below +/-
4500 or +/-3000W Secondary are pinned at +/-4500 or +/-3000W Secondary, respectively.
Total VA (Point 12)
This point is formatted as a 2's complement fraction. It represents a fraction of 4500W Secondary
in normal operation, or 3000W Secondary in Open Delta operation. Inputs above/below +/-4500 or
+/-3000W Secondary are pinned at +/-4500 or +/-3000W Secondary, respectively.
Power Factor (Point 13)
This point is formatted as a 2's complement integer. It represents Power Factors from -1.000
(0x0FC18) to +1.000 (0x003E8). In Open Delta operation, Total Power Factor (Point 13) is always
zero.
Frequency (Point 14)
This point is formatted as a 2's complement fraction. It represents the Frequency as measured on
Phase A Voltage in units of cHz (centiHertz, 1/100 Hz). Inputs below 45.00 Hz are pinned at 0
(0x0000); inputs above 75.00 Hz are pinned at 9999 (0x270F).
11
Total VAR
Point
Reading
12
Total VA
Point
Reading
13
Power Factor Total
Point
Reading
14
Frequency
Point
Reading
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...