DPF700

Dual Relay Option Board

for the DPF700 Meter

www.omega.com  

e-mail: [email protected]

User’s Guide

Shop on line at

 

Summary of Contents for DPF700

Page 1: ...DPF700 Dual Relay Option Board for the DPF700 Meter www omega com e mail info omega com User sGuide Shop on line at...

Page 2: ...FAX 203 359 7700 e mail info omega com Canada 976 Bergar Laval Quebec H7L 5A1 TEL 514 856 6928 FAX 514 856 6886 e mail info omega ca For immediate technical or application assistance USA and Canada S...

Page 3: ...manual M1676 NOTES and CAUTIONS Information that is especially important to note is identified by these labels NOTE WARNING CAUTION IMPORTANT NOTE provides you with information that is important to su...

Page 4: ...ARD 2 2 2 SETTING UP THE DUAL RELAY OPTION BOARD 3 2 3 ELECTRICAL CONNECTION 5 3 1 RELAY OUTPUT OPTION BOARD SPECIFICATIONS 6 FIGURES 2 1 DUAL RELAY OPTION BOARD 2 2 2 SETPOINT EXAMPLE ILLUSTRATION 4...

Page 5: ...rations This option card is intended for use in a DPF700 panel mount device that is protected in accordance with Class I of EN 61010 115 230 AC power connections Installation of this instrument should...

Page 6: ...g this option board 1 Hold the board in a horizontal position with the TB3 connector facing towards the rear of the meter 2 Line up the 3 connectors located on the back side of the board with pin grou...

Page 7: ...tpoint HI HYSTERESIS Relay 2 is energized when display value is more than Setpoint HI Relay 2 is not energized when display value is less than Setpoint LO Setpoint Example Setpoint HI is 500 0 and Set...

Page 8: ...to latched setpoints set software switch 2 of the configuration menu to 1 ConFIG X1XXXX When relays are energized they stay energized until a Reset either front panel or back connector reset STANDARD...

Page 9: ...y 1 TB3 3 is a common contact of relay 1 TB3 4 is a normally closed contact of relay 2 TB3 5 is a normally open contact of relay 2 TB3 6 is a common contact of relay 2 Figure 2 3 Electrical Wiring for...

Page 10: ...3 1 RELAY OUTPUT OPTION BOARD SPECIFICATIONS 2 Form C on off relays Configurable for latched and unlatched by software Max Current 5 Amps resistive load Max Voltage 250 Vac or 28 Vdc tion D NOTES aul...

Page 11: ...MEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Shou...

Page 12: ...s Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps...