IQ 150S
B: Modbus Map
IM02601006E www.eaton.com MM-7
Description
1
Format
Range
6
Units or
Resolution
Comments
#
Reg
Modbus Address
Hex
Decimal
7548 - 7548
30025 - 30025
Reserved
1
7549 - 7549
30026 - 30026
COM2 setup
UINT16
bit-mapped
----dddd -ppp-bbb
1
754A - 754A
30027 - 30027
COM2 address
UINT16
1 to 247
none
1
754B - 754B
30028 - 30028
Reserved
1
754C - 754C
30029 - 30029
Reserved
1
754D - 754D
30030 - 30030
Reserved
1
754E - 754E
30031 - 30031
Reserved
1
754F - 754F
30032 - 30032
Reserved
1
7550 - 7554
30033 - 30037
5
7555 - 7559
30038 - 30042
5
755A - 755E
30043 - 30047
5
755F - 7563
30048 - 30052
5
7564 - 7568
30053 - 30057
5
7569 - 756D
30058 - 30062
5
756E - 7572
30063 - 30067
5
Block Size:
68
read-only except as noted
9C40 - 9C40
40001 - 40001
System Sanity Indicator
UINT16
0 or 1
none
0 indicates proper meter operatio
1
9C41 - 9C41
40002 - 40002
Volts A-N
UINT16
2047 to 4095
volts
2047= 0, 4095= +150
1
9C42 - 9C42
40003 - 40003
Volts B-N
UINT16
2047 to 4095
volts
1
9C43 - 9C43
40004 - 40004
Volts C-N
UINT16
2047 to 4095
volts
1
9C44 - 9C44
40005 - 40005
Amps A
UINT16
0 to 4095
amps
0= -10, 2047= 0, 4095= +10
1
9C45 - 9C45
40006 - 40006
Amps B
UINT16
0 to 4095
amps
1
9C46 - 9C46
40007 - 40007
Amps C
UINT16
0 to 4095
amps
1
9C47 - 9C47
40008 - 40008
Watts, 3-Ph total
UINT16
0 to 4095
watts
0= -3000, 2047= 0, 4095= +3000
1
9C48 - 9C48
40009 - 40009
VARs, 3-Ph total
UINT16
0 to 4095
VARs
watts, VARs, VAs =
1
9C49 - 9C49
40010 - 40010
VAs, 3-Ph total
UINT16
2047 to 4095
VAs
3000 * (register - 2047) / 2047
1
9C4A - 9C4A
40011 - 40011
Power Factor, 3-Ph total
UINT16
1047 to 3047
none
1047= -1, 2047= 0, 3047= +1
pf = (register - 2047) / 1000
1
9C4B - 9C4B
40012 - 40012
Frequency
UINT16
0 to 2730
Hz
0= 45 or less, 2047= 60, 2730= 65 or more
freq = 45 + ((register / 4095) * 30)
1
9C4C - 9C4C
40013 - 40013
Volts A-B
UINT16
2047 to 4095
volts
2047= 0, 4095= +300
1
9C4D - 9C4D
40014 - 40014
Volts B-C
UINT16
2047 to 4095
volts
1
9C4E - 9C4E
40015 - 40015
Volts C-A
UINT16
2047 to 4095
volts
1
dddd = reply delay (* 50 msec)
ppp = protocol (1-Modbus RTU, 2-Modbus
ASCII, 3-DNP)
amps = 10 * (register - 2047) / 2047
12-Bit RTU Readings Section
12-Bit RTU Block
volts = 150 * (register - 2047) / 2047
volts = 300 * (register - 2047) / 2047
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...