IM02601006E www.eaton.com 5-27
IQ 150S/250S 5: Communication
Transformer/Line Loss Compensation
Transformer/Line Loss Compensation allows you to add or subtract losses to meter registration.
From the Tree Menu, click Revenue & Energy Settings>Transformer/Line Loss
Compensation.
This screen displays the current values for the meter's Transformer Loss Compensation. The
screen fields and acceptable entries are as follows
• Percent Loss of Watts due to Iron and Copper/Positive Watts and Negative Watts
• Percent Loss of VARS due to Iron and Copper/Positive and Negative Watts
• Drop-down menu #1. Choose from: Disabled, Fe Only, Cu Only, Both Fe and Cu.
• Drop-down menu #2. Choose from: Add to Watts and VAR; Add to Watts and Subtract from VAR;
Subtract from Watts and Add to VAR; Add to Watts and VAR; Subtract from Watts and VAR.
1. Click
TLC Calculator
to find the values to enter into the Percent Loss fields. The TLC Calculator
button launches an Excel Spreadsheet that makes the calculations for you once you enter the
required data.
WARNING!
Eaton Meter Configuration Software automatically launches the Excel Spreadsheet
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...