IM02601006E www.eaton.com B-27
IQ 150S/250S B: Modbus Map
occurs when current index is 91 (the 8'th window). There are now 9 records available (100-91),
so make Records per Window equal 9.
11. Repeat steps 5 through 10.
NOTES
:
• Go back to step 5, where a couple of values have changed.
Pass CurIndex FirstRecIndex RecPerWindow
0 0 0 13
1 13 13 13
2 26 26
13
3 39 39
13
4 52 52
13
5 65 65
13
6 78 78
13
7 91 91
9
8 100 ------
-------
• At pass 8, since Current Index is equal to the number of records (100), log retrieval should stop;
go to step 12 (see step 9 Notes).
12. No more records available, clean up.