IQ 150S/250S B: Modbus Map
1. Read [0xC757, 16 reg], Historical Log 1 Header Block.
Send:
0103 C757 0010
Command
:
Register Address:
0xC757
# Registers:
16
---------------------------------------------------
Receive
:
010320 00000100 00000064 0012 0000
060717101511 060718101511
0000000000000000
Data
:
Max Records:
0x100 = 256 records maximum.
Num Records:
0x64 = 100 records currently logged.
Record Size:
0x12 = 18 bytes per record.
Log Availability:
0x00 = 0, not in use, available for retrieval.
First Timestamp:
0x060717101511 = July 23, 2006, 16:21:17
Last Timestamp:
0x060717101511 = July 24, 2006, 16:21:17
NOTE
: This indicates that Historical Log 1 is available for retrieval.
2. Write 0x0280 -> [0xC34F, 1 reg], Log Enable.
Send
:
0106 C34F 0280
Command
:
Register Address:
0xC34F
# Registers:
1 (Write Single Register Command)
Data
:
Log Number:
2 (Historical Log 1)
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...