IM02601006E www.eaton.com B-23
IQ 150S/250S B: Modbus Map
4. Compute #RecPerWin as (246\18)=13. Write 0x0D01 0000 0000 -> [0xC350, 3 reg] Write
Retrieval Info. Set Current Index as 0.
Send
:
0110 C350 0003 06 0D01 00 000000
Command
:
Register Address:
0xC350
# Registers:
3, 6 bytes
Data
:
Records per Window:
13. Since the window is 246 bytes, and the record
is 18 bytes, 246\18 = 13.66, which means that
13 records evenly fit into a single window. This is
234 bytes, which means later on, we only need to
read 234 bytes (117 registers) of the window to
retrieve the records.
# of Repeats:
1. We are using auto-increment (so not 0), but
not function code 0x23.
Window Status:
0 (ignore)
Record Index:
0, start at the first record.
----------------------------------------------------
Receive
:
0110C3500003 (command ok)
NOTES
:
• This sets up the window for retrieval; now we can start retrieving the records.
• As noted above, we compute the records per window as 246\18 = 13.66, which is rounded to 13
records per window. This allows the minimum number of requests to be made to the meter,
which increases retrieval speed.
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...