IM02601006E www.eaton.com B-12
IQ 150S/250S B: Modbus Map
Log Retrieval Header:
The Log Retrieval Header is used to program the log to be retrieved, the record(s) of that log to be
accessed, and other settings concerning the log retrieval.
Registers:
0xC34F - 0xC350
Size:
2 registers
• Log Number: The log to be retrieved. Write this value to set which log is being retrieved.
0
System Events
1
Alarms
2
Historical Log 1
3
Historical Log 2
4
Historical Log 3
Bytes
Value
Type
Format
Description
# Bytes
0-1
Log Number,
Enable,
Scope
UINT16
nnnnnnnn esssssss
nnnnnnnn -
log to
retrieve,
e - retrieval
session
enable
sssssss -
retrieval
mode
2
2-3
Records per
Window,
Number of
Repeats
UINT16
wwwwwwww nnnnnnnn
wwwww-
www -
records per
window,
nnnnnnnn -
repeat count
2
Summary of Contents for IQ 150S
Page 4: ......
Page 14: ...IM02601006E www eaton com 1 4 IQ 150S 250S 1 Introduction This page intentionally left blank...
Page 93: ...IM02601006E www eaton com 5 43 IQ 150S 250S 5 Communication XY Graph Advanced Graph...
Page 116: ...IM02601006E www eaton com 5 66 IQ 150S 250S 5 Communication This page intentionally left blank...
Page 192: ...IQ 150S B Modbus Map IM02601006E www eaton com MM 10 This page intentionally left blank...
Page 208: ...IQ 250S B Modbus Map IM02601006E www eaton com MM 16 This page intentionally left blank...
Page 222: ...IM02601006E www eaton com C 14 IQ 150S C DNP Map This page intentionally left blank...
Page 234: ...IM02601006E www eaton com D 10 IQ 250S D DNP Map This page intentionally left blank...