3
|
Components
Service manual
233
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
a
a
Compressor wire terminals cover
9
Add
refrigerant
to
the
refrigerant
circuit,
see
368].
Install the crankcase heater, see
"To install the crankcase heater"
10
Install the compressor insulation, see
227].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the compressor insulation
b
c
e
d
b
Strip
c
Top jacket
d
Body jacket
e
Compressor
1
Install the body jacket (d) on the compressor (e).
2
Install the top jacket (c).
3
Attach the strip (b) to the top jacket (c).