3
|
Components
Service manual
227
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
3.3.2 Repair procedures
To remove the transportation stay (only for 14+16 HP)
The transportation stays for protecting the unit during transport must be removed.
Proceed as shown in the figure and procedure below.
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
1
Slightly loosen the bolt (a).
2
Remove the transportation stay (b) as shown in the figure below.
3
Tighten the bolt (a) again.
1
3
2
1
3
3
3
2
(x2)
(×2)
1
2
1
2
a
b
a
(12.3 N·m)
To remove the transportation stay (only for 18+20 HP)
The transportation stays for protecting the unit during transport must be removed.
Proceed as shown in the figure and procedure below.
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
1
Slightly loosen the bolt (a).
2
Remove the transportation stay (b) as shown in the figure below.
3
Tighten the bolt (a) again.
4
Slightly loosen the bolt (c).
5
Remove the bolt (d) of the transportation stay (e).
6
Remove the transportation stay (e) as shown in the figure below.
7
Tighten the bolt (c) again.