6
|
Technical data
Service manual
462
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
N°
(
*
)
Item
Display
Content
(
**
)
14
Additional refrigerant charge
amount
2.14
0
"Additional refrigerant charge
18
Outdoor unit fan high static pressure
setting
2.18
0
Deactivated
1
Activated
20
Additional refrigerant charge
operation
2.20
0
Off
1
On
21
Refrigerant recovery mode
2.21
0
Off
1
On
22
Nighttime low noise operation level
setting (combined with 2-26 and
2-27) [level1 > level2 > level3]
2.22
0
Off
1
Level 1
2
Level 2
3
Level 3
25
Low noise operation level setting (if
LNO triggered by external input)
(combined with 2-12) [level1 > level2
> level3]
2.25
1
Level 1
2
Level 2
3
Level 3
26
Nighttime low noise operation start
time setting (combined with 2-22)
2.26
1
20h00
2
22h00
3
24h00
27
Nighttime low noise operation stop
time setting (combined with 2-22)
2.27
1
6h00
2
7h00
3
8h00
28
Power transistor check mode
2.28
0
Off
1
On
29
Capacity priority in low noise
operation mode
2.29
0
Off
1
On
30
Level setting for demand control
step 1
2.30
1
60%
2
65%
3
70%
4
75%
5
80%
6
85%
7
90%
8
95%
31
Level setting for demand control
step 2
2.31
1
40%
2
50%
3
55%
Summary of Contents for VRV IV+