Troubleshooting
Service manual
130
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.116 LC-30-31-32 – Transmission abnormality main PCB/inverter PCB A6P
Main error code
Sub error code
Unit
LC
30
Main
31
Sub 1
32
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
No transmission between
main PCB and inverter
PCB A6P .
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB or wrong capacity setting.
2
Perform a check of the noise filter PCB A2P. See
298].
Possible cause:
Faulty noise filter PCB A2P.
3
Perform a check of the inverter PCB A3P. See
274].
Possible cause:
Faulty inverter PCB A3P.
4
Perform a check of the noise filter PCB A5P. See
298].
Possible cause:
Faulty noise filter PCB A5P.
5
Perform a check of the inverter PCB A6P. See
274].
Possible cause:
Faulty inverter PCB A6P.
6
Check the wiring between the PCB's. See
385].
Possible cause:
Faulty wiring between PCB's.
7
Check if the correct spare part is installed for all PCB's. See checking
procedures of the specific PCB's.
Possible cause:
Wrong spare part PCB installed.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.