Troubleshooting
Service manual
149
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
INFORMATION
Main PCB checks L1‑N on connector X1A for sinus waveform each time crossing the
zero‑line. Interval between each zero‑crossing is 10 miliseconds when the power
supply is 50 Hz.
1
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
3
Perform a check of the inverter PCB(s). See
Possible cause:
Faulty inverter PCB(s).
4
Perform a check of the noise filter PCB. See
298].
Possible cause:
Faulty noise filter PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.142 U2-01-08-11 – Inverter circuit power supply abnormality - inverter PCB A3P abnormal
voltage
Main error code
Sub error code
Unit
U2
01
Main
08
Sub 1
11
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.