3
|
Components
Service manual
268
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
a
a
Fuse
Blown fuse on the fan inverter PCB?
Action
Yes
Replace the fan inverter PCB, see
269].
No
PCB and continue with the next
procedure.
To perform a power transistor check of the fan inverter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
1
Set the multimeter to diode measurement.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
2
Check the fan inverter PCB in reference with the tables below.
d’
d
a
b
c
e f g
c’
e’ f’ g’