Troubleshooting
Service manual
79
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Trigger
Effect
Reset
Ambient temperature
thermistor R1T read-out is
out of range.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
thermistor read-out is
within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor air thermistor. See
348].
Possible cause:
Faulty ambient air thermistor.
2
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.56 HA-00 – Defrost fail alarm
Trigger
Effect
Reset
When outdoor unit judges
defrost is not completed.
Unit keeps running.
Auto reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the required space around the outdoor unit heat exchanger. See
372].
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
2
Clean the outdoor heat exchanger. See
374].
Possible cause:
Dirty outdoor heat exchanger.
3
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
4
Perform a check of the de–icer thermistor. See
348].
Possible cause:
Faulty de–icer thermistor or connector fault.
5
Perform a check of the refrigerant high pressure sensor. See
Possible cause:
Faulty refrigerant high pressure sensor.