6
|
Technical data
Service manual
459
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
N°
(
*
)
Item
Display
Content
10
Number of indoor units
1.10
Shows total amount of connected indoor units
on a single F1/F2 in line. Possible 0 ˜ 63
13
Number of outdoor units
1.13
Shows total amount of outdoor units
connected on a single F1/F2 out line. Possible
0 ˜ 63
15
Number of units in zone
1.15
Possible 0 ˜ 63
16
Number of all indoor units
1.16
Shows total amount of indoor units of several
systems if F1/F2 out is wired between
systems. Possible 0 ˜ 128
17
Latest error code
1.17
Displays latest error causing forced stop
18
2nd latest error code
1.18
Displays 2nd latest error causing forced stop
19
3rd latest error code
1.19
Displays 3rd latest error causing forced stop
20
Software ID upper code
1.20
Use set (BS2 ) to view full code
21
Outdoor unit capacity
1.21
0
No data
3
8 HP
4
10 HP
5
12 HP
6
14 HP
7
16 HP
8
18 HP
9
20 HP
22
Software id lower code
1.22
Displays lower code for software ID
23
Latest retry
1.23
Displays latest reason causing retry
24
2nd latest retry
1.24
Displays 2nd latest reason causing retry
25
3rd latest retry
1.25
Displays 3rd latest reason causing retry
26
Number of D3Net transmission retry
1.26
Possible 0 ˜ 63
27
Number of ACCNS transmission retry
1.27
Possible 0 ˜ 63
28
Number of outdoor units on a multi
system
1.28
Number of outdoor units on Q1/ Q2 line in
multi combination
29
Result of last manual refrigerant leak
check
1.29
Possible 0 ˜ 9.9
30
Result of 2nd last manual refrigerant
leak check
1.30
Possible 0 ˜ 9.9
31
Result of 3rd last manual refrigerant
leak check
1.31
Possible 0 ˜ 9.9
32
Outdoor board status judgement
1.32
0
Standart judgement
1
Normal
2
Abnormal
33
Number of abnormal outdoor board
status judgement
1.33
Possible 0 ˜ 15
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......
Page 476: ...ESIE18 15B 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...