Service manual
262
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Blown fuse on the fan inverter PCB?
Action
No
PCB and continue with the next
procedure.
To perform a power transistor check of the fan inverter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
1
Set the multimeter to diode measurement.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
2
Check the fan inverter PCB in reference with the tables below.
c
a
b
d e f
a
Fan inverter PCB A4P
b
Connector P1
c
Connector N1
d
Connector X1A, pin U
e
Connector X1A, pin V
f
Connector X1A, pin W
VDC
Com
Ref
VDC
Com
Ref
P1
X1A, pin U
O.L
N1
X1A, pin V
0,45
P1
X1A, pin V
O.L
N1
X1A, pin W
0,45
P1
X1A, pin W
O.L
X1A, pin U
N1
O.L
X1A, pin U
P1
0,45
X1A, pin V
N1
O.L
X1A, pin V
P1
0,45
X1A, pin W
N1
O.L
X1A, pin W
P1
0,45
P1
N1
O.L
N1
X1A, pin U
0,45
N1
P1
0,75
Are the test results OK?
Action
Yes
Power transistors are OK. Return to
No
Replace the fan inverter PCB, see
263].
Problem solved?
After all checking procedures listed above have been performed: