Troubleshooting
Service manual
140
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Trigger
Effect
Reset
Main PCB detects other
type PCB than set in
EEPROM or wrong dip
switch setting on spare
part main PCB.
Unit will stop operating.
Manual reset via user
interface.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the correct spare part is installed for the main PCB. See
290]. Check dips switch setting for spare part main PCB.
Possible cause:
Incorrect spare part main PCB or incorrect dips switch setting.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
3
Perform a check of the inverter PCB A3P. See
274].
Possible cause:
Faulty inverter PCB A3P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.131 PJ-09-15-16 – Capacity setting mismatch for fan inverter PCB A4P
Main error code
Sub error code
Unit
PJ
09
Main
15
Sub 1
16
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Main PCB detects other
type PCB than set in
EEPROM or wrong dip
switch setting on spare
part main PCB.
Unit will stop operating.
Manual reset via user
interface.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.