6
|
Technical data
Service manual
468
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Mode
1
st
code
Description function
2
nd
code
Description selection
12(22)
0
Optional board KRP1A… output
X1X2
01
Indoor unit turned ON by
thermostat
02
--
03
Operation output
04
Malfunction output
05
--
1
T1T2 input signal
01
Forced OFF
02
ON/OFFcontrol
03
External protection device input
04
Forced OFF - multi tenant
2
Thermostat differential to set
point
01
1.0°C (FXFQ, FXZQ, FXCQ, FXKQ,
FXUQ, FXHQ, VKM, Biddle
02
0.5°C (FXSQ, FXMQ, FXAQ, FXLQ,
FXNQ, FXDQ, EKEQM)
3
OFF by thermostat fan speed
01
LL
02
Set fan speed
03
OFF
4
Automatic mode differential
01
0°C
02
1°C
03
2°C
04
3°C
05
4°C
06
5°C
07
6°C
08
7°C
5
Auto restart after power failure
01
Disabled
02
Enabled
6
Fan speed in cooling thermo OFF
01
LL
02
Set speed
03
OFF
9
Forced C/H master
01
Disabled (select by cool / heat
selection button controller)
02
ON (not possible by cool / heat
selection button controller)
Summary of Contents for VRV IV+