2
|
Troubleshooting
Service manual
52
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
Faulty auto charge expansion valve.
3
Perform
a
check
of
all
refrigerant
side
thermistors.
See
Possible cause:
Faulty refrigerant side thermistor(s).
4
Perform a check of the refrigerant low pressure sensor. See
Possible cause:
Faulty refrigerant low pressure sensor.
5
Check if the refrigerant circuit is correctly charged. See
363].
Possible cause:
Refrigerant overcharge.
6
Check if the power supply is conform with the regulations. See
356].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
7
Perform a power reset. If the error disappears and is raised again after a
while, check for the presence of an external source causing electrical noise.
See
372].
Possible cause:
External source may cause interference.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.31 E9-44-45-46 – Electronic expansion valve (Y3E) failure
Main error code
Sub error code
Unit
E9
44
Main
45
Sub 1
46
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Lower heat exchanger
expansion valve Y3E
malfunction.
Unit will stop operating.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.