3
|
Components
Service manual
255
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Expansion
valve
name
Symbol
Connector
Winding
resistance
BS4Q-A
BS6Q-A
BS8Q-A
BS10Q-A
BS12Q-A
BS16Q-A
Suction gas
pipe
Y37E
X21A
150 ±15 Ω
✔
HP/LP gas
pipe
Y38E
X22A
150 ±15 Ω
Subcool
Y39E
X23A
46 ±3 Ω
Suction gas
pipe
Y40E
X24A
150 ±15 Ω
✔
HP/LP gas
pipe
Y41E
X25A
150 ±15 Ω
Subcool
Y42E
X26A
46 ±3 Ω
Suction gas
pipe
Y43E
X27A
150 ±15 Ω
✔
HP/LP gas
pipe
Y44E
X28A
150 ±15 Ω
Subcool
Y45E
X29A
46 ±3 Ω
Suction gas
pipe
Y46E
X30A
150 ±15 Ω
✔
HP/LP gas
pipe
Y47E
X31A
150 ±15 Ω
Subcool
Y48E
X32A
46 ±3 Ω
INFORMATION
Below is an example of the resistance measurements in which the common wire is
connected to pin 6 of the expansion valve motor connector. Connections may differ
according to the type of expansion valve.
▪
Connector pin 1‑6,
▪
Connector pin 2‑6,
▪
Connector pin 3‑6,
▪
Connector pin 4‑6.
a
a
Connector
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......
Page 476: ...ESIE18 15B 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...