2
|
Troubleshooting
Service manual
94
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Gas thermistor R6T after
subcool heat exchanger
short/open circuit.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
thermistor read-out is
within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the gas pipe thermistor of the subcool heat exchanger. See
Possible cause:
Faulty gas pipe thermistor of the subcool heat exchanger.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.76 J9-08-09-10 – Gas thermistor R6T abnormality
Main error code
Sub error code
Unit
J9
08
Main
09
Sub 1
10
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Gas thermistor R6T after
subcool heat exchanger is
out of range.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
thermistor read-out is
within range.