2
|
Troubleshooting
Service manual
169
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
5
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
6
Check the F1‑F2 transmission line between the indoor units and outdoor unit.
See
Possible cause:
Faulty or interruption in transmission line between indoor
units and outdoor unit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.168 UA-00 – Combination abnormality
Trigger
Effect
Reset
Combination abnormality. Forced stop.
Power reset and only
allowed combination.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Change the installation with ONLY R410A type indoor units.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.169 UA-03 – Combination abnormality - Mix of R22, R407C and R410A type units detected
Trigger
Effect
Reset
Mix of R22, R407C, R410A
type units detected.
Forced stop.
Power reset and only
allowed combination.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Change the installation with ONLY R410A type indoor units.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.