Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
2
Loosen and remove the screw using an Allen key.
3
Remove the axle cover.
4
Pull the propeller fan blade from the fan motor axle.
c
b
d
a
e
a
Screw
b
Allen key
c
Axle cover
d
Propeller fan blade assembly
e
Pulley remover
INFORMATION
Use a pulley remover if the propeller cannot be removed manually.
5
To install the propeller fan blade assembly, see
To remove the DC fan motor assembly
1
Remove the propeller fan blade assembly from the DC fan motor assembly,
see
308].
2
Disconnect the DC fan motor connector from the fan inverter PCB.
3
Unlock the ferrite bead.
4
Cut the tie strap.
5
Detach the DC fan motor cable.