3
|
Components
Service manual
223
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
The compressor dampers may look different.
Compressor dampers and piping are in
a good condition?
Action
Yes
Perform an electrical check of the
compressor, see
221].
No
Replace the compressor, see
To perform an electrical check of the compressor
1
First perform a mechanical check of the compressor, see
221].
2
[Hz] = [rps] x (number of poles) / 2:
▪
For K-Type Compressor: [Hz] = 3 x [rps]
▪
For G-Type Compressor: [Hz] = 2 x [rps]
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
356].
3
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
4
Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.