2
|
Troubleshooting
Service manual
134
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A3P detects
open or short circuit or
out of range on fin
thermistor.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when fin
temperature is within
range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
fin
thermistor
of
the
PCB.
See
348].
Possible cause:
Faulty fin thermistor of the PCB.
1
Check the required space around the outdoor unit heat exchanger. See
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
2
Perform a check of the liquid cooling expansion valve. See
244].
Possible cause:
Faulty liquid cooling expansion valve.
3
Perform a check of the inverter PCB A3P. See
274].
Possible cause:
Faulty inverter PCB A3P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.122 P4-02-15-17 – Fin thermistor abnormality on fan inverter PCB A4P
Main error code
Sub error code
Unit
P4
02
Main
15
Sub 1
17
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.