2
|
Troubleshooting
Service manual
117
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
356].
2
Check that the thermal interface grease is applied properly on the (PCB or
refrigerant piping) contact surface of the heat sink. Adjust if needed.
Possible cause:
Thermal interface grease NOT applied properly on the heat
sink.
3
Check if heat sink plate is correctly fixed with screws.
Possible cause:
Heat sink plate not correctly installed.
4
Check (by touching) if refrigerant is flowing through the radiant cooling
refrigerant circuit. The radiant cooling refrigerant circuit should be warm if
refrigerant is flowing. If no refrigerant flow, perform a check of the liquid
cooling expansion valve, see
244].
Possible cause:
No refrigerant flow through the radiant cooling refrigerant
circuit.
5
Perform a check of the liquid cooling expansion valve. See
Possible cause:
Faulty liquid cooling expansion valve.
6
Check ambient temperature. Check if outdoor unit location temperature
differs drastically.
7
Check if there is discharge air by-pass on installation location.
Possible cause:
External noise. Check further on how to eliminate external
factors.
8
Perform a check of the fan inverter PCB A7P. See
Possible cause:
Faulty fan inverter PCB A7P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.103 L4-09-10-11 – Inverter PCB A6P high fin temperature
Main error code
Sub error code
Unit
L4
09
Main
10
Sub 1
11
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.