2
|
Troubleshooting
Service manual
186
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
No input at field setting 2–14 (2–14 = 0) when field setting 2–
88 = 0.
2
Set field setting 2–88 to 0, see
455] to enable the
outdoor unit to perform long test run to be able to judge refrigerant amount.
3
Check if test run was interrupted.
4
using the error based troubleshooting, see
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.199 E-2 – Refrigerant leak check cannot be performed - indoor air temperature is out of range
Trigger
Effect
Reset
Average indoor unit air
temperature <15°C.
Unit will NOT start
refrigerant leak check
mode.
Perform refrigerant leak
check when average
indoor temperature
>15°C.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the indoor unit air thermistors. See service manual of the
respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit air thermistor(s).
2
Perform refrigerant leak check when the average indoor temperature is above
15°C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.200 E-3 – Refrigerant leak check cannot be performed - outdoor air temperature is out of range
Trigger
Effect
Reset
Outdoor air temperature
<20°C.
Unit will NOT start
refrigerant leak check
mode.
Perform refrigerant leak
check when average
outdoor temperature
>20°C.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor air thermistor. See
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......