62-11039
7-47
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
95
CHECK COND FAN CONTACTOR 1
•
TRIGGER–ON: Condenser fan motor contactor coil (CDCON) current is more than 5 Amps
•
UNIT CONTROL: Engine and standby operation: alarm only
•
UNIT CONTROL: Engine and standby operation: alarm only.
•
RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check CDCON
a. Inspect condenser fan contactor coil
and terminals
No damage to coil
No damaged or corroded pins
b. Check contactor coil resistance
Cannot be opened (infinite ohms); Shorted (Zero Ohms)
or shorted to ground
c. Check amp draw of coil.
Refer to Section 2.14. Use ammeter.
2.
Check CDCON Current Draw
a. Use Component Test Mode (Refer to
Section 5.2.5.2.2) to test actual current
draw of the circuit.
Refer to Section 2.14 for normal current values.
View current draw in Data List.
3.
Check CDCON
a. Inspect harness & control box
connector pins & terminals (See
wiring schematic)
See Notes 2 & 6
No physical damage to harness.
No damaged or corroded pins
96
CHECK GENERATOR CONTACTOR
•
TRIGGER–ON: Generator contactor relay coil (GENCONR) current is more than 5 Amps
•
UNIT CONTROL: Engine and standby operation: alarm only
•
UNIT CONTROL: Engine and standby operation: alarm only.
•
RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check GENCONR
a. Inspect generator contactor relay coil
and terminals
No damage to coil
No damaged or corroded pins
b. Check contactor coil resistance
Cannot be opened (infinite ohms); Shorted (Zero Ohms)
or shorted to ground
c. Check amp draw of coil.
Refer to Section 2.14. Use ammeter.
2.
Check GENCONR Current Draw
a. Use Component Test Mode (Refer to
Section 5.2.5.2.2) to test actual current
draw of the circuit.
Refer to Section 2.14 for normal current values.
View current draw in Data List.
3.
Check GENCONR Wiring
a. Inspect harness & control box
connector pins & terminals (See
wiring schematic)
See Notes 2 & 6
No physical damage to harness.
No damaged or corroded pins
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...