62-11039
5-3
5.2.1 Configuration Mode
NOTE
To enter Configuration Mode Refer to Section
5.2.
a. “
↑ ↓
TO SCROLL, THEN = TO SELECT” will appear
in the MessageCenter.
b. Press the UP ARROW Key to scroll through the Con-
figuration list beginning at the top.
Press the DOWN ARROW Key to scroll through the
Configuration list beginning at the bottom.
c. To read through the Configuration list, continue to
press either the UP or DOWN ARROW keys. The list
is circular meaning that once the end is reached, it is
repeated from the beginning.
d. To change one of the Configurations, bring the Con-
figuration to change into the MessageCenter, and
press “=”.
↑ ↓
TO SCROLL, THEN = TO SAVE” will
show in the MessageCenter for 10 seconds Then the
selected Configuration will flash, showing the current
value. Press the UP or DOWN ARROW Key to scroll
through the list of available selections for this Config-
uration.
e. Once a new value is showing in the MessageCenter,
press the = Key to save the selection. The
MessageCenter will stop flashing. The new value is
now in memory.
f. Press the UP ARROW Key to continue to scroll
through the Configuration list.
CONFIGURATION
SELECTIONS
DESCRIPTION
UNIT MODEL NUMBER #
Pick one of these two models from
the Vector model family
NDP33GN6HBV2
NDP33GN6HBV3
The correct model number must be selected for
proper operation and control. This is also part of
the Unit Data where user can read the information.
Configuration mode is the only way user can write
information.
UNIT SERIAL NUMBER #
The unit S/N may be entered. This may be up to
10 characters long. Numbers, Letters, and a space
are available by scrolling through the available list.
TRAILER ID #
The ID # may be entered. This may be up to 10
characters long. Numbers, Letters, and a space
are available by scrolling through the available list.
SET NEW HOURS
Hours from existing micro can be installed into re-
placement micro.
GLOW TIME
SHORT
LONG
Indicates to the controller how long to energize the
glow plugs
LONG = Longer glow times are used
SHORT= Shorter glow times are used.
NOTE: Refer to Section 4.1.1 for glow time table.
OUT OF RANGE SHUTDOWN:
(Refer to Section 2.8.3)
YES /
NO
YES = When the box temperature has been out--
of--range for 45 minutes, the alarm light will come
on, and the unit will shut down.
NO = When the box temperature has been out--of--
range for 30 minutes, the alarm light will come on
and the unit will continue to run.
PARAMETERS LOCKOUT:
YES /
NO
YES = All Functional Parameters in the function list
are locked in place.
NO = All Functional Parameters in the function list
can be changed using the keypad, unless individu-
ally locked out by Reefer Manager.
RPM ALARM SHUTDOWN:
YES /
NO
YES = When alarm 39 is active the alarm light will
be on and the engine will shut off.
NO = When alarm 39 is active the alarm light will
be on and the engine will continue to run.
LOW PRESSURE SHUTDOWN:
YES
/ NO
YES = When alarm 18 is active the alarm light will
be on and the unit will shut off.
NO = When alarm 18 is active the alarm light will
be on and the unit continue to run.
LP SHUTDOWN DELAY:
255 SECS
(0 -- 255 seconds)
After the Low Pressure signal is received, how long
shall the unit continue to run before it is shut down.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...