62-11039
7-23
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
35
CHECK STARTER CIRCUIT
•
TRIGGER–ON: Engine speed fails to reach 50 RPM during 2 start attempts.
•
UNIT CONTROL: Engine operation:engine and unit shutdown and alarm. Standby operation: this alarm
UNIT CONTROL: Engine operation:engine and unit shutdown and alarm. Standby operation: this alarm
will not activate in standby operation.
•
RESET CONDITION: Change unit to standby operation or alarm may be manually reset via keypad or by
turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue
with the steps below as necessary.
1.
Check Starter Relay Circuit
a. Check operation of starter solenoid
relay
Energize Circuit. (See Note 2)
Relay contacts closed when SSR85 is grounded.
b. Check relay socket and terminals
No signs of discoloration from overheating
No corrosion
c. Check voltage to starter solenoid relay Negative lead on 85, Positive lead on 86 = 12 VDC
Negative lead on Gnd, Positive lead on 87 & 30 = 12 VDC
d. Inspect wiring to starter solenoid and
starter motor
No physical damage to wiring or battery cable end.
No damaged or corroded terminals.
e. Check voltage to starter solenoid
Must be above 11.5 VDC
f. Check voltage to starter motor
Must be above 10 VDC while cranking
2.
Check Starter
a. Inspect starter and wiring
No damage or corrosion
Wiring and battery cable must be clean and tight
b. Check resistance of starter motor
See Section 2.14
c. Check amperage draw of starter
See Section 2.14
3.
Check Battery Voltage
a. Inspect battery cable ends and posts
Must be clean and tight
No corrosion
b. Test voltage at battery with unit off
Must be above 11 VDC
c. Test specific gravity of battery
Check
d. Perform load test on battery (Follow
battery manufacturer’s procedure)
Check
4.
Check For Correct Engine Oil
a. Check for correct oil viscosity (weight)
for conditions
Refer to Section 2.9
Must be correct for ambient conditions
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...