62-11039
5-11
CONFIGURATION
SELECTIONS
DESCRIPTION
HIGH SPEED DELAY
1 MIN
0 TO 10 MINUTES
IN 0.5 MINUTE IN-
CREMENTS
Select the length of time unit remains in low speed
before transitioning to high speed.
SATELLITE COMM
(Optional)
(NOT SUPPORTED IN VECTOR
MT)
This feature is not supported for Vector MultiTemp
models at this time.
UNIT OPERATION:
STANDARD
RAIL
STANDARD = The microprocessor is set to control
trailer refrigeration operation.
RAIL = Not recommended for Vector MT
ENABLE INTELLISET AT = KEY
NO
YES
YES = Allows access to the Intelliset menu using
the = key.
NO = Allows access to the Intelliset menu using the
SELECT key.
SUPPLY AIR LIMIT FOR S/S
10.4
°
F TO +32
°
F
(--12
°
C to +0
°
C)
(in 0.5
°
F or
°
C in-
crements)
DEFAULT: 21.2
°
F
(--6
°
C)
Coldest allowable supply air temperature for
Compartment 1 when unit is running in Start/Stop.
SUPPLY AIR LIMIT FOR CONT
10.4
°
F TO +32
°
F
(--12
°
C to +0
°
C)
(in 0.5
°
F or
°
C in-
crements)
DEFAULT: 23
°
F
(--5
°
C)
Coldest allowable supply air temperature for
Compartment 1 when unit is running in Continuous.
SAT2 (Optional and available for 2
Compartment Units)
NOT INSTALLED
(0)
INSTALLED (1)
NOT INSTALLED-- Supply Air Temperature Sensor
is not installed in Compartment 2 evaporator.
INSTALLED -- Supply Air Temperature Sensor is
installed in Compartment 2 evaporator.
C2 SUPPLY AIR LIMIT FOR S/S
10.4
°
F TO +32
°
F
(--12
°
C to +0
°
C)
(in 0.5
°
F or
°
C in-
crements)
DEFAULT: 26.6
°
F
(--3
°
C)
Coldest allowable supply air temperature for
Compartment 2 when unit is running in Start/Stop.
C2 SUPPLY AIR LIMIT FOR CONT
10.4
°
F TO +32
°
F
(--12
°
C to +0
°
C)
(in 0.5
°
F or
°
C in-
crements)
DEFAULT: 30.2
°
F
(--1
°
C)
Coldest allowable supply air temperature for
Compartment 2 when unit is running in Continuous.
HIGH SPEED PULLDOWN
ON /
OFF
When active, this logic indicates if temperature lim-
its regulating the exit of pulldown mode are modi-
fied or not.
ON = Allows for high speed cool pulldown when
only one compartment is configured.
OFF = Normal unit operation.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...