7-28
62-11039
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
40
CHECK GLOW PLUGS
•
TRIGGER–ON: During engine startup glow plug amperage is less than 30 Amps, or greater than
43 Amps after 13 seconds of glow time (NOTE: In auto start, this can only occur when the Engine
Coolant Temperature is below 32
°
F (0
°
C) and the glow time is configured SHORT.)
•
UNIT CONTROL: Engine operation: alarm only Standby operation: this alarm will not activate in standby
•
UNIT CONTROL: Engine operation: alarm only. Standby operation: this alarm will not activate in standby
operation.
•
RESET CONDITION: Auto Reset if glow plug amperage is between 30 to 43 amps for at least
13 seconds during the glow cycle or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Glow Plug Circuit
a. Inspect glow plug relay & socket
No signs of discoloration from overheating
No corrosion
b. Check operation of Glow Plug Relay
Energize circuit. (See Note 2). Put GPR on GPR85.
LED 30 must be ON
c. Check Non–Running Amps
View Current Draw in Data List
Refer to Section 2.14.
Energize GPR using component test mode.
d. Check Glow Plug circuit amperage
Current Draw = Non–Running Amps + Glow Plug Amps
e. Check voltage to glow plugs
Must be 11 VDC or higher
2.
Check Glow Plug Circuit Wiring
a. Inspect harness & control box
connector pins & terminals (See wiring
schematic)
No physical damage to harness.
No damaged or corroded pins
3.
Check Glow Plugs
a. Check amp draw of each glow plug
Refer to Section 2.14
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...