62-11039
5-9
CONFIGURATION
SELECTIONS
DESCRIPTION
RANGE (1--2) MINIMUM TEMP
--22
°
F TO +
89.6
°
F
(--30
°
C to +
32
°
C)
in 0.1
°
F or
°
C in-
crements
Select the lowest temperature desired for either
Range 1 and/or Range 2.
RANGE (1--2) MAXIMUM TEMP
--22
°
F TO +
89.6
°
F
(--30
°
C to +
32
°
C
)
in 0.1
°
F or
°
C in-
crements
Select the highest temperature desired for either
Range 1 and/or Range 2.
MIN SETPOINT
C2 MIN SETPOINT
C3 MIN SETPOINT
--22
°
F
TO +89.6
°
F
(--30
°
C to +30
°
C)
in 0.1
°
F or C incre-
ments
Select the lowest temperature that will ever be used
as setpoint. Setpoint can not be set lower than this
value.
MAX SETPOINT
C2 MAX SETPOINT
C3 MAX SETPOINT
--22
°
F TO +
89.6
°
F
(--30
°
C to +
32
°
C
)
in 0.1
°
F or
°
C in-
crements
Select the highest temperature that will ever be
used as setpoint. Setpoint can not be set higher
than this value.
NO POWER
NOT INSTALLED /
INSTALLED &
SHUTDOWN
SWITCH TO EN-
GINE
NOT INSTALLED -- Standby operation is not
installed
INSTALLED & SHUTDOWN -- Standby is installed.
If standby power is lost unit will shut down
SWITCH TO ENGINE -- Standby is installed. If
standby power is lost diesel engine will start.
S/S PARAMETERS
TOGETHER
SEPARATE
TOGETHER = When the Minimum Run Time, Mini-
mum Off Time, Maximum Off Time, and Override
Temperatures are set in the Functional Parameter
List, the same values will be used for both Frozen
and Perishable setpoints.
SEPARATE = When the Minimum Run Time, Mini-
mum Off Time, Maximum Off Time, and Override
Temperatures are set in the Functional Parameter
List, different values may be entered for Perishable
and Frozen setpoints.
REMOTE TEMP SENSOR 1
(Optional)
REMOTE TEMP SENSOR 2
(Optional and Available for 2
Compartment Units Only)
ON /
OFF
ON=A remote sensor has been added to the unit,
and connected into the wire harness at Remote
Temp Sensor (1--2) plug. This enables Remote
Temp Sensor ( 1--2) to be read through the Data
List.
OFF=There is no Remote Sensor (1--2) in this unit.
DOOR SWITCH:
(Optional)
NOT AVAILABLE FOR 3
COMPARTMENT UNITS
SWITCH NOT
INSTALLED
DOOR OPEN
SWITCH OPEN
DOOR OPEN
SWITCH CLOSED
SWITCH NOT INSTALLED = There is no door
switch in this box.
DOOR OPEN SWITCH OPEN = A Door Switch has
been installed on one of the box doors. The switch
contacts will be OPEN whenever the door is OPEN.
DOOR OPEN SWITCH CLOSED = A Door Switch
has been installed on one of the box doors. The
switch contacts will be CLOSED whenever the door
is OPEN.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...