7-20
62-11039
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
7.5 START UP/ENGINE ALARMS
30
FAILED TO RUN MINIMUM TIME
•
TRIGGER–ON: Engine has shut down on an alarm 3 times without having run for at least 15 minutes
between each shutdown (not including Door or Remote Switch shut downs) AND
unit is in automatic start mode
unit is in automatic start mode.
•
UNIT CONTROL: Engine operation: engine and unit shutdown and alarm. Standby operation:
refrigeration system shutdown and alarm with PSCON still energized.
•
RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue
with the steps below as necessary.
1
Check For Alarms
a. Check for shut down alarms
Alarm conditions must be corrected and the alarm(s)
cleared to continue.