5.6.7 Configuration/IntelliSet Card
a. Place the RS in the Off position to power down the
microprocessor and to take it out of Configuration
Mode.
b. Power the microprocessor up by either turning the
RS to the Start/Run position (ok to place in Manual
Start Operation if desired), or by inserting a PC Mode
jumper into the Download Port.
c. Insert your Configuration PC Card into the PC Card
slot in the microprocessor and watch the
MessageCenter. When the MessageCenter shows
“CFG, = TO LOAD,
↑
TO CANCEL”, press the
= Key. It will take 10 – 15 seconds to load the Intelli-
Sets off the card. “LOADING INFO” will be displayed
during this time. When finished, the MessageCenter
will show “ALL INFO LOADED – REMOVE CARD”.
Remove the PC Config Card.
d. If the unit is not equipped with the IntelliSet Option, or
there is only a single set of settings on the PC Card,
the MessageCenter will show
“MICRO WILL RESET AND RESTART NOW”.
NOTE
Units with IntelliSet will not automatically reset
and shutdown when the PC Card is removed,
as do units without IntelliSet. Units with
IntelliSet will NOT indicate ANY change in oper-
ating parameters UNTIL an IntelliSet is selec-
ted
e. Press the = Key to display default IntelliSet. (Enable
IntelliSet at = Key must be configured ON.
See
Section 5.2.1.
)
f. Default Intelliset will appear in the MessageCenter.
Press either the UP or Down Arrow keys to move
through the IntelliSet List. Move to the desired Intel-
liSet and press the = Key. The desired IntelliSet is
automatically active.
5.6.8 Microprocessor Final Checkout
a. Start the unit and allow it to run for a few minutes.
b. While the unit is running, scroll through the Data List
of the microprocessor. Verify that all the data that
was recorded in Step b. of Section 5.6.1 is now accu-
rately displayed in the Data List. Also, verify that the
correct date and time is being displayed.
c. Initiate a Pretrip test. Allow the unit to complete the
Pretrip and check for any alarms. Make any neces-
sary repairs before returning the unit into service.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...