8-3
62-11039
e. Oil Change Intervals
Oil Type
Oil Change/ESI Filter Change
Petroleum
3000 hours/2 yrs
Synthetic*
4000 hours /2 yrs
* Mobil Delvac1 is the only approved synthetic oil. Maximum oil drain interval is two (2) years.
These maintenance schedules are based on the use of
approved oils and regular Pretrip inspections of the unit.
Failure to follow the recommended maintenance
schedule may affect the life and reliability of the
refrigeration unit.
8.2 PRETRIP INSPECTION
The following pretrip inspection should be performed
before every trip and at regular maintenance intervals.
BEFORE STARTING ENGINE
Drain water from bottom of fuel tank
Drain water from water separator on fuel
filter (if applicable)
Check radiator coolant level
Check condenser coil for cleanliness
Check radiator coil for cleanliness
Check air cleaner and hoses
Check engine oil level
Check condition of water pump belt
Check battery fluid level (if applicable)
Check battery cables and terminals
Check evaporator coil(s) for cleanliness
Check bulkhead and return air screen
Check all defrost water drains
Place in Continuous Run, and start unit.
IMMEDIATELY AFTER STARTING EN-
GINE
Check fuel lines and filters for leaks
Check oil lines and filters for leaks
Check coolant hoses for leaks
Check exhaust system for leaks
Check condenser fan for proper airflow.
Check evaporator fan for proper airflow.
Check for unusual noises
PRETRIP
Initiate Pre--Trip
List any Pre--trip Alarms
AFTER OPERATING UNIT FOR 15
MINUTES OR MORE
Check refrigerant level
Check compressor oil level
Check for proper temperature control
Check auto--start/stop operation
Initiate defrost and allow to terminate
Check engine speeds
OPERATE IN HIGH SPEED COOL
AND RECORD
(From Microprocessor Unit Data List)
SUCTION PRESSURE . . . . . . . . . . . . . .
DISCHARGE PRESSURE . . . . . . . . . . . .
ENGINE COOLANT TEMP . . . . . . . . . . .
C1 RETURN AIR TEMP . . . . . . . . . . . . . .
C2 RETURN AIR TEMP . . . . . . . . . . . . . .
C3 RETURN AIR TEMP . . . . . . . . . . . . . .
AMBIENT AIR TEMP . . . . . . . . . . . . . . . .
DEFROST TERM TEMP #1 . . . . . . . . . .
DEFROST TERM TEMP #2 . . . . . . . . . .
DEFROST TERM TEMP #3 . . . . . . . . . .
COMP DISCH TEMP . . . . . . . . . . . . . . . .
CSMV % . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXV % . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BATTERY VOLTAGE . . . . . . . . . . . . . . . .
DC CURRENT DRAW . . . . . . . . . . . . . . .
ENGINE RPM . . . . . . . . . . . . . . . . . . . . . .
SOFTWARE REVISION . . . . . . . . . . . . . .
CONTROL SERIAL # . . . . . . . . . . . . . . . .
UNIT MODEL # . . . . . . . . . . . . . . . . . . . . .
HOURS TO ENGINE MAINTENANCE .
HOURS TO UNIT MAINTENANCE . . . .
TIME LEFT TO PM1 . . . . . . . . . . . . . . . . .
TIME LEFT TO PM2 . . . . . . . . . . . . . . . . .
TIME LEFT TO PM3 . . . . . . . . . . . . . . . . .
TIME LEFT TO PM4 . . . . . . . . . . . . . . . . .
TIME LEFT TO PM5 . . . . . . . . . . . . . . . . .
DATALOGGER TIME & DATE . . . . . . . .
FINAL
Review Functional Parameters
Download recorder data (if required)
Enter Trip Start in Micro
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...