62-11039
7-33
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
53
TEMP OUT--OF--RANGE (Continued)
NOTE: For Condition One, the temperature criteria for this alarm is reset, and the box temperature must again go
In--Range before this alarm can be triggered if any of the following occur:
•
pre--trip is started
•
Setpoint is changed
•
A door switch or remote switch is installed and configured as a door switch
NOTE: The15, 30, or 45 minute timer is reset and starts again whenever:
S
The unit cycles off and restarts in Start--Stop
S
The unit goes into and comes out of Defrost
NOTE: This alarm does not go into the Inactive alarm List when it becomes inactive or is cleared.
NOTE: This alarm will not be used in Sleep Mode
54
DEFROST NOT COMPLETE
•
TRIGGER–ON: Defrost cycle did not complete within 45 minutes
•
UNIT CONTROL: Engine and standby operation: alarm only. While this alarm is active, the Defrost Timer
UNIT CONTROL: Engine and standby operation: alarm only. While this alarm is active, the Defrost Timer
will be set to initiate a defrost cycle 90 minutes (1.5 hours) of unit running time after the alarm comes on.
•
RESET CONDITION: Auto Reset when defrost cycle is started again, or alarm may be manually reset via
keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Perform Pre--trip Check
a. Run pre--trip & check for alarms
Any active alarms must be corrected and cleared before
proceeding.
2.
Check For Defective Defrost Sensor Location/ Correct Installation
a. Has sensor fallen from location
Must be corrected to continue
3.
Check Evaporator Fan Contactor
a. Check that contactor is in operation in
defrost
Must disengage fan during defrost
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...