8-30
62-11039
8.19.2 Checking High Pressure Switch
WARNING
Do not use a nitrogen cylinder without a
pressure regulator. Cylinder pressure is
approximately 2350 PSIG (159.9 Bar). Do
not use oxygen in or near a refrigerant sys-
tem as an explosion may occur.
(See
Figure 8--32)
1
2
3
4
5
6
1. Cylinder Valve
and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge
[0 to 400 PSIG (0 to
27.2 Bar)]
5. Bleed-Off Valve
6. 1/4 inch Connection
Figure 8--32. Typical Setup for Testing High
Pressure Switch
a. Remove switch as outlined in Section 8.19.1
b. Connect ohmmeter or continuity light across switch
terminals. Ohmmeter will indicate resistance and
continuity light will be lighted if switch closed after re-
lieving pressure.
c. Connect switch to a cylinder of dry nitrogen. (See
Figure 8--32)
d. Set nitrogen pressure regulator higher than cutout
point on switch being tested. Pressure switch cutout
and cut-in points are shown in Section 2.12.
e. Close valve on cylinder and open bleed-off valve.
f. Open cylinder valve. Slowly close bleed-off valve and
increase pressure until the switch opens. If light is
used, light will go out and if an ohmmeter is used, the
meter will indicate open. Open pressure on gauge.
Slowly open bleed-off valve (to decrease pressure)
until switch closes (light will light or ohmmeter will
move).
8.20 DISCHARGE PRESSURE TRANSDUCER
(CDP)
HIGH RANGE PRESSURE TRANSDUCER
-- CDP
OUT
P
UT
V
O
LT
A
GE
W
IT
H
5V
SU
PPL
Y
(VO
LT
S)
PRESSURE (PSIG)
Figure 8--33. Pressure Transducer Values
Table 8-4 Suction and discharge
Pressure Transducer Voltages
Psig
Bar
Suction
voltage
Discharge
voltage
--14.5
- 1.0
0.50
0.38
--8.7
- 0.6
0.66
0.42
0
0
1.01
0.50
5
0.3
1.19
0.54
10
0.6
1.36
0.58
15
1.0
1.54
0.62
20
1.3
1.71
0.66
25
1.7
1.88
0.70
30
2.0
2.06
0.74
35
2.4
2.23
0.78
40
2.7
2.41
0.82
45
3.0
2.58
0.86
50
3.4
2.76
0.90
55
3.7
2.93
0.94
60
4.1
3.10
0.98
65
4.4
3.28
1.02
70
4.8
3.45
1.06
75
5.1
3.63
1.10
80
5.4
3.80
1.14
85
5.8
3.98
1.18
90
6.1
4.15
1.22
95
6.5
4.32
1.26
100
6.8
4.50
1.30
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...