62-11039
7-115
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
234 UNIT SERIAL # ERROR
•
TRIGGER–ON: There is an error in the Unit Serial Number that is stored in the microprocessor memory
TRIGGER ON: There is an error in the Unit Serial Number that is stored in the microprocessor memory
•
UNIT CONTROL: Unit Shutdown & Alarm
•
RESET CONDITION: Auto Reset only when a valid Model number is entered.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Unit Serial Number
a. Check
Model
Number
in
microprocessor
Must be a valid Model Number from Configuration List.
microprocessor
b. Enter correct Model Number
From Configuration List, select correct Model Number.
2.
Reset Microprocessor
a. Turn RS off for 30 seconds, then turn
back on.
Microprocessor powers up OK
Valid number is present
b. Check for valid Model number in Data
List.
Valid number is present.
Alarm is cleared
R l
i
c. Valid model number can not be
entered.
Replace microprocessor
235 CONTROL SERIAL # ERROR
•
TRIGGER–ON: There is an error in the Microprocessor Serial Number that is stored in the
microprocessor memory
microprocessor memory
•
UNIT CONTROL: Unit Shutdown & Alarm
•
RESET CONDITION: Auto Reset only when a valid Model number is entered.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Microprocessor Serial Number
a. Check
Model
Number
in
microprocessor
Must be a valid Model Number from Configuration List.
microprocessor
b. Enter correct Model Number
From Configuration List, select correct Model Number.
2.
Reset Microprocessor
a. Turn RS off for 30 seconds, then turn
back on.
Microprocessor powers up OK
Valid number is present
b. Check for valid Model number in Data
List.
Valid number is present.
Alarm is cleared
R l
i
c. Valid model number can not be
entered.
Replace microprocessor
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...