9-5
62-11039
INDICATION/
TROUBLE
POSSIBLE CAUSES
REFERENCE
SECTION
9.3 ALTERNATING CURRENT GENERATOR
Loss of residual magnetism in exciter field
8.9
No voltage
Circuit breaker tripped
Check
No voltage
Open or short in stator windings
Check
Short circuited
Repair
Low engine speed
Correct
Low voltage
Excessive load
Check
Low voltage
High resistance connections -- connections
warm or hot
Clean and
Tighten
Fluctuating speed
Correct
Fluctuating voltage
Irregular speed of engine
Engine Manual
Fluctuating voltage
Loose terminal or load connections
Tighten
High voltage
Excessive engine speed
Correct
Generator overloaded
Check
Overheating
Clogged ventilation openings
Clean
Overheating
Insufficient circulation
Check Fan
Unbalanced load
Balance
Mechanical Noise
Loose laminations
8.9.2
Generator frame produces shock
when touched
Static charge
Check ground
to frame