62-11039
3-17
3.13 VIEW INACTIVE ALARMS
COOL
DEFROST
ALARM
START-STOP
SETPOINT
BOX TEMPERATURE
ALARM LIST
SELECT
MANUAL
DEFROST
HEAT
CONTINUOUS
NO INACTIVE ALARMS
+36 F
-20
START--STOP/
CONTINUOUS
2
1. Press and hold both the ALARM LIST key and the UP ARROW key for 6
seconds. If there are no inactive alarms, the display will say
“NO INACTIVE ALARMS” for 5 seconds.
2. If there are inactive alarms, the display will be ‘I’ and the alarm number and
message.
3. Press the ALARM LIST or UP or DOWN key to scroll through the list of alarms.
4. When you reach the end of the alarm list, “LIST END, = TO CLEAR ALARMS”
is displayed for 5 seconds.
5. To clear the active and inactive alarm list, press the = key while
“LIST END, = TO CLEAR ALARMS” is being displayed. “ALL ALARMS CLEAR” is displayed.
The microprocessor can hold up to 16 alarms within the
Active and Inactive Alarm Lists combined. The list can
be read via the MessageCenter or using the
ReeferManager PC Program. There are 2 sections in
the Alarm List, an Active Alarm Section and Inactive
Alarm Section. Alarms in these sections are in the order
in which the alarms activate and deactivate,
respectively. On startup, all alarms are marked as
inactive in the entire list. If an inactive alarm becomes
active, the alarm is moved from the Inactive Alarm List
(section) to the Active Alarm List (section).
As additional alarms occur, they will be placed first in the
Active Alarm List. An alarm can not be active and
inactive at the same time. Each alarm can only be
present in either the Active or Inactive Alarm List at any
given time. As conditions changed, alarms may be
moved from the Active Alarm List to the Inactive alarm
list and back.
Alarms are also recorded in the Data Recorder. They
are recorded at the time they occur (become active),
and the time they become inactive.
For a complete list of Alarms and troubleshooting
information Refer to Section 7.
TIP
When alarms are cleared from the Inactive
Alarm List, both active and inactive alarm lists
are cleared.
If there is a safety shutdown,
UNIT SHUTDOWN -- SEE
ALARM LIST
will be shown. See Section 7 for complete
list of Alarms and their descriptions.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...