62-11039
7-17
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
23
A/C CURRENT OVER LIMIT (Continued)
8.
Check High Voltage Components Amp Draw
a. Check condenser fan amp draw on all
3 legs.
b. Check evaporator fan motor amp draw
for Compartment 1 on all 3 legs.
c. Check evaporator fan motor amp draw
for Compartment 2 on all 3 legs.
d. Check evaporator fan motor amp draw
for Compartment 3 on all 3 legs.
e. Check compressor amp draw on all
3 legs.
f. Check Compartment 1 Heater amp
draw for HTCON1
See Section 2.13
g. Check Compartment 1 Heater amp
draw for HTCON2
h. Check Compartment 1 Heater amp
draw for 2HTCON1
i. Check Compartment 1 Heater amp
draw for 2HTCON2
j. Check Compartment 1 Heater amp
draw for 3HTCON1
k. Check Compartment 1 Heater amp
draw for3HTCON2