62-11039
7-19
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
28
CHECK REFRIGERATION SYSTEM
•
TRIGGER ON: The refrigeration system is running and the discharge pressure is less than 5 PSIG
(0.34 Bar) higher than suction pressure for more than 10 minutes
•
UNIT CONTROL: Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown
and alarm. Standby operation: alarm only or (if configured for shutdown) refrigeration system shutdown
and alarm with PSCON still energized.
•
RESET CONDITION: Auto reset when discharge pressure is more than 20 PSIG (1.36 Bars) above the
suction pressure when in alarm only, or auto reset after 15 minutes when shutdown is configured or alarm
may be manually reset via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Verify Compressor Is Running.
a. Check compressor Amp draw -- CCON
T1--T2, T1--T3, T2--T3.
2.
Check System Pressures
a. Install Manifold Test Set and check and
compare compressor discharge &
suction pressures with those shown on
the microprocessor controller.
Suction pressure must be above 3 PSIG (0.2 Bar)
Suction & Discharge Pressures must have the same
reading on gauges & on micro display.
NOTE: Microprocessor suction pressure reading has
a maximum value of 100 psig (7.5 bar)
3.
Perform Pre--trip Check
a. Run pre--trip & check for alarms
Any active alarms must be corrected and cleared before
proceeding.
4.
Check Compressor.
a. Perform Pump--Down Test.
See Section 8.10.1
Must pump down to 5 PSI and hold for minimum of 1
minute.
b. Cover condenser and build--up
discharge pressure.
Must be able to pump up to 400 PSI.
c. Disassemble and inspect compressor
valve plates, reeds, pistons, etc.
Must be intact, clean, and in good working order.
Summary of Contents for VECTOR 1800 MT
Page 1: ......
Page 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Page 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Page 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Page 21: ...1 7 62 11039 ...
Page 303: ...10 1 62 11039 ...
Page 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Page 311: ...10 9 62 11039 FROM PREVIOUS SHT ...