Device Name
The Device Name is a text field that names the sensor. It is used in traps, e-mails and on the EventSensor
Status page. The maximum length is 60 characters.
Any of the options in the sensor point options in the Internal Events Menu will open a configuration page for
that sensor point. This manual will go over only contact closures as an example. The Contact Closures listed
in the Internal Events Menu are the two IO points, which can be configured as Contact points.
EventSensor Reporting Enabled
This is an ON/OFF toggle to enable a sensor to report to another TeleBoss over a network connection using
Contact Closure Setup
Contact Closures (CC) sense the state of a circuit. A weak voltage is applied to the source pin and if pulled to
ground by a connection on the circuit, the sensor reports a "closed" state. If it remains high, the sensor reports
an "open" state. The contact closures may be configured to alarm in either the open or closed state,
depending on the needs of the attached devices.
TeleBoss 830 - Internal Contact Closure Event 1
A) Sensor Name [unnamed]
B) Contact Closure Enabled [OFF]
C) Event State [CLOSED]
D) Event Threshold [2]
E) Return to Normal Threshold [2]
F) Event State Actions []
G) Return to Normal Actions []
H) Event State Class [Info]
I) Return to Normal Class [Info]
J) Event Trap Number [110]
K) Return to Normal Trap Number [110]
L) Active Alarm Alias []
M) Inactive Alarm Alias []
N) Override Global Reminder Interval [OFF]
O) Individual Reminder Interval (minutes) [120]
Sensor Name
An alphanumeric field that allows you to name this contact closure. The maximum length is 60 characters.
The default setting is ‘unnamed’.
Contact Closure Enabled
This is an ON/OFF toggle to enable this contact closure. The default setting is OFF.
Event State
This is an OPEN/CLOSED toggle that determines whether an event will be triggered when the contact closure
circuit is opened or closed. The default state is CLOSED.
Event / Return to Normal Threshold
A field that sets the number of seconds (0-255) the sensor must remain in, or be out of, the event state before
an event action occurs. The default setting is 2 seconds.