TeleBoss 830 2.11.370 STD User Manual
Page 110
Sensor Unresponsive Settings
The Sensor Unresponsive Menu is where you can configure the actions the TeleBoss takes if an
EventSensor becomes unresponsive.
TeleBoss 830 - Sensor Unresponsive Menu
A) Sensor Unresponsive Timeout [30]
B) Sensor Unresponsive Actions []
C) Sensor Unresponsive Trap Number [50]
D) Sensor Unresponsive Class [Info]
Sensor Unresponsive Timeout
This sets the time (10 - 65535 seconds) to wait before declaring a non-communicative EventSensor
unresponsive. The default setting is 30.
Sensor Unresponsive Actions
Choosing this option displays the Actions List, a menu where the action string for the event is configured.
This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to
for more information.
Sensor Unresponsive Trap Number
This sets the trap number to be sent with any SNMP traps for this event. The default is 50, but the trap
number can also be set in the range of 1000
– 1199 as needed.
Sensor Unresponsive Class
Use this option to set the class for the alarm. When this option is selected, a list of the classes previously
is displayed. Select one to be assigned to this event. The default is Info.
General Sensor Unresponsive Settings as accessed via Web UI
The Senor Unresponsive settings would be accessed from the EventSensor submenu under the Events
section on the left hand menu. The settings described above are located at the bottom of the page
EventSensor Settings page.