TeleBoss 830 2.11.370 STD User Manual
Page 75
TeleBoss 830 - CPE Pages
A) CPE Page 1 (CPEs 1-16)
B) CPE Page 2 (CPEs 17-32)
C) CPE Page 3 (CPEs 33-48)
D) CPE Page 4 (CPEs 49-64)
Enter your Selection:
TeleBoss 830 - CPE Settings
A) CPE 1 [0.0.0.0]
.. . .
P) CPE 16 [0.0.0.0]
Enter your Selection:
TeleBoss 830 - CPE 1 Settings
A) IP Address [0.0.0.0]
B) Name []
C) Description []
D) Alarm Keep-alive Period (seconds) [0]
E) Alarm Threshold [1]
F) Alarm Reminder Interval (minutes) [0]
IP Address
This field sets the IP address of the device to monitor. The value is a dotted quad IP address. The default
setting is 0.0.0.0
Name
This field sets a name for the equipment. The only restriction on the name is that it cannot have any single or
double quotes ( ' or " ) in it. The maximum length is 24 characters.
Description
This field is a description of what the device is. The only restriction on the description is that it cannot have
any single or double quotes ( ' or " ) in it. The maximum length is 64 characters.
Alarm Keep-alive Period (seconds)
This field sets the number of seconds between periodic pings (ping cycle) sent by the TeleBoss to the defined
device to make sure it is "alive“. 1 ping frame is transmitted per CPE per ping cycle. Values are: 0 to 65535.
The default setting is 0.
Alarm Threshold
This option sets the number of times that the unit receives no response to the keep-alive ping from the device
before triggering the CPE down event. Values are: 1 to 255. The default setting is 1.
Alarm Reminder Interval (minutes)
This field sets the number of minutes for the associated device to be unresponsive before a reminder alarm is
sent. The reminder alarm shares the same event configuration (actions/trap number/class) as a CPE Down
event, but includes the text “Reminder“. 0 means no reminder event is configured. The default setting is 0.
CPE Settings as accessed via Web UI
On the Web Interface the CPE settings are called Ping Alarms. All of the settings to configure Ping Alarms
can be access from the Device Management Page.