Enable EventSensor Reporting Host
This is
an ON/OFF toggle to enable this TeleBoss to be a host for EventSensor reporting from another
Asentria device. Default setting is OFF.
EventSensor Reporting Host Port
This is used
to set the TCP Port that this TeleBoss will use for receiving sensor reports from another Asentria
device. Default setting is 4000.
SNMP Settings
The SNMP Settings option displays a menu where you can enable the SNMP agent and configure community
names.
Testing SNMP Traps
Using the command interface enter the command
DOTRAP
from the command prompt. Verify that the trap
manager receives the test trap.
TeleBoss 830 - SNMP Settings
A) SNMP Agent Enable [OFF]
B) Read Community [public]
C) Write Community [public]
D) Trap Community [public]
SNMP Agent Enable
This option toggles between ON and OFF. It controls whether the unit responds to SNMP gets and sets. The
default setting is OFF.
Note
: SNMP Agent Enable does NOT stop SNMP traps from being sent when it is set to OFF.
Read / Write / Trap Community
These fields set the SNMP trap community names. The default setting for all is “public“. The maximum length
for each is 23 characters.
Note:
SNMP traps are
not
a guaranteed means of delivering notifications. Traps are a one-way IP
network datagram and the device receiving traps does not acknowledge them. Therefore, if the trap does
not reach its intended destination for whatever reason, the sending device has no way of recognizing this
and resending the trap.
SNMP Settings as accessed via Web UI
These same SNMP settings can be configured using the Web GUI, by navigating to Networking in the
Settings Menu and selecting SNMP.
There is no way to do a
DOTRAP
command test from the web interface.