Asterion DC Multioutput Series
Programming Manual
M330517-01 Rev C
10-59
Constant Current Operation, Constant Power Operation and Foldback Mode
Operation bits. If these bits are not enabled in the protection enable register, then
mode changes shall not cause a shutdown.
Figure 10-1 shows the implementation of the Protection Status Register,
Protection Enable Register and Protection Event Register. To configure the Power
Supply to generate service requests based on the Protection Event Status Register,
program both the Protection Event Status Enable Register and the Service Request
Enable Register (*SRE). See 10.2.2 and Section 14 SCPI Status Implementation
for more details.
Bit
Hex Value
Description
0
0x01
Constant Voltage Operation
1
0x02
Constant Current Operation
2
0x04
Constant Power Operation
3
0x08
Overvoltage Protection Fault
4
0x10
Over Temperature Fault
5
0x20
External Shutdown
6
0x40
Foldback Mode Operation
7
0x80
Remote Programming Error
8
0x100
Fan Fault
9
0x200
Line Drop Fault
10
0x400
DC Module Fault
11
0x800
PFC Fault
12
0x1000
OCP Fault
13
0x2000
AUX Supply Fault
14
0x4000
Line Status Changed
15
0x8000
Not Used
16
0x10000
Remote Sense Fault
17-31
Not Used (Always returns zero for these bits)
Table 10-1: Protection Condition and Event Status Registers
Summary of Contents for Sorensen Asterion DC ASM
Page 1: ...M330517 01 Rev C Asterion DC Multioutput Series Programming Manual...
Page 6: ...Asterion DC Multioutput Series Programming Manual M330517 01 Rev C v SAFETY SYMBOLS...
Page 145: ...Asterion DC Multioutput Series Programming Manual 13 128 M330517 01 Rev C CAL n LOCK...
Page 162: ...M330461 01 Rev C 14 145...